OPC UA Client Listener Input Plugin
This service plugin receives data from an OPC UA server by subscribing to nodes and events.
Introduced in: Telegraf v1.25.0 Tags: iot OS support: all
Service Input
This plugin is a service input. Normal plugins gather metrics determined by the interval setting. Service plugins start a service to listen and wait for metrics or events to occur. Service plugins have two key differences from normal plugins:
- The global or plugin specific
interval
setting may not apply - The CLI options of
--test
,--test-wait
, and--once
may not produce output for this plugin
Global configuration options
In addition to the plugin-specific configuration settings, plugins support additional global and plugin configuration settings. These settings are used to modify metrics, tags, and field or create aliases and configure ordering, etc. See the CONFIGURATION.md for more details.
Secret-store support
This plugin supports secrets from secret-stores for the username
and
password
option.
See the secret-store documentation for more details on how
to use them.
Configuration
# Retrieve data from OPCUA devices
[[inputs.opcua_listener]]
## Metric name
# name = "opcua_listener"
#
## OPC UA Endpoint URL
# endpoint = "opc.tcp://localhost:4840"
#
## Maximum time allowed to establish a connect to the endpoint.
# connect_timeout = "10s"
#
## Behavior when we fail to connect to the endpoint on initialization. Valid options are:
## "error": throw an error and exits Telegraf
## "ignore": ignore this plugin if errors are encountered
# "retry": retry connecting at each interval
# connect_fail_behavior = "error"
#
## Maximum time allowed for a request over the established connection.
# request_timeout = "5s"
#
# Maximum time that a session shall remain open without activity.
# session_timeout = "20m"
#
## The interval at which the server should at least update its monitored items.
## Please note that the OPC UA server might reject the specified interval if it cannot meet the required update rate.
## Therefore, always refer to the hardware/software documentation of your server to ensure the specified interval is supported.
# subscription_interval = "100ms"
#
## Security policy, one of "None", "Basic128Rsa15", "Basic256",
## "Basic256Sha256", or "auto"
# security_policy = "auto"
#
## Security mode, one of "None", "Sign", "SignAndEncrypt", or "auto"
# security_mode = "auto"
#
## Path to cert.pem. Required when security mode or policy isn't "None".
## If cert path is not supplied, self-signed cert and key will be generated.
# certificate = "/etc/telegraf/cert.pem"
#
## Path to private key.pem. Required when security mode or policy isn't "None".
## If key path is not supplied, self-signed cert and key will be generated.
# private_key = "/etc/telegraf/key.pem"
#
## Authentication Method, one of "Certificate", "UserName", or "Anonymous". To
## authenticate using a specific ID, select 'Certificate' or 'UserName'
# auth_method = "Anonymous"
#
## Username. Required for auth_method = "UserName"
# username = ""
#
## Password. Required for auth_method = "UserName"
# password = ""
#
## Option to select the metric timestamp to use. Valid options are:
## "gather" -- uses the time of receiving the data in telegraf
## "server" -- uses the timestamp provided by the server
## "source" -- uses the timestamp provided by the source
# timestamp = "gather"
#
## The default timetsamp format is RFC3339Nano
# Other timestamp layouts can be configured using the Go language time
# layout specification from https://golang.org/pkg/time/#Time.Format
# e.g.: json_timestamp_format = "2006-01-02T15:04:05Z07:00"
#timestamp_format = ""
#
#
## Client trace messages
## When set to true, and debug mode enabled in the agent settings, the OPCUA
## client's messages are included in telegraf logs. These messages are very
## noisey, but essential for debugging issues.
# client_trace = false
#
## Include additional Fields in each metric
## Available options are:
## DataType -- OPC-UA Data Type (string)
# optional_fields = []
#
## Node ID configuration
## name - field name to use in the output
## namespace - OPC UA namespace of the node (integer value 0 thru 3)
## identifier_type - OPC UA ID type (s=string, i=numeric, g=guid, b=opaque)
## identifier - OPC UA ID (tag as shown in opcua browser)
## default_tags - extra tags to be added to the output metric (optional)
## monitoring_params - additional settings for the monitored node (optional)
##
## Monitoring parameters
## sampling_interval - interval at which the server should check for data
## changes (default: 0s)
## queue_size - size of the notification queue (default: 10)
## discard_oldest - how notifications should be handled in case of full
## notification queues, possible values:
## true: oldest value added to queue gets replaced with new
## (default)
## false: last value added to queue gets replaced with new
## data_change_filter - defines the condition under which a notification should
## be reported
##
## Data change filter
## trigger - specify the conditions under which a data change notification
## should be reported, possible values:
## "Status": only report notifications if the status changes
## (default if parameter is omitted)
## "StatusValue": report notifications if either status or value
## changes
## "StatusValueTimestamp": report notifications if either status,
## value or timestamp changes
## deadband_type - type of the deadband filter to be applied, possible values:
## "Absolute": absolute change in a data value to report a notification
## "Percent": works only with nodes that have an EURange property set
## and is defined as: send notification if
## (last value - current value) >
## (deadband_value/100.0) * ((high–low) of EURange)
## deadband_value - value to deadband_type, must be a float value, no filter is set
## for negative values
##
## Use either the inline notation or the bracketed notation, not both.
#
## Inline notation (default_tags and monitoring_params not supported yet)
# nodes = [
# {name="node1", namespace="", identifier_type="", identifier=""},
# {name="node2", namespace="", identifier_type="", identifier=""}
# ]
#
## Bracketed notation
# [[inputs.opcua_listener.nodes]]
# name = "node1"
# namespace = ""
# identifier_type = ""
# identifier = ""
# default_tags = { tag1 = "value1", tag2 = "value2" }
#
# [[inputs.opcua_listener.nodes]]
# name = "node2"
# namespace = ""
# identifier_type = ""
# identifier = ""
#
# [inputs.opcua_listener.nodes.monitoring_params]
# sampling_interval = "0s"
# queue_size = 10
# discard_oldest = true
#
# [inputs.opcua_listener.nodes.monitoring_params.data_change_filter]
# trigger = "Status"
# deadband_type = "Absolute"
# deadband_value = 0.0
#
## Node Group
## Sets defaults so they aren't required in every node.
## Default values can be set for:
## * Metric name
## * OPC UA namespace
## * Identifier
## * Default tags
## * Sampling interval
##
## Multiple node groups are allowed
#[[inputs.opcua_listener.group]]
## Group Metric name. Overrides the top level name. If unset, the
## top level name is used.
# name =
#
## Group default namespace. If a node in the group doesn't set its
## namespace, this is used.
# namespace =
#
## Group default identifier type. If a node in the group doesn't set its
## namespace, this is used.
# identifier_type =
#
## Default tags that are applied to every node in this group. Can be
## overwritten in a node by setting a different value for the tag name.
## example: default_tags = { tag1 = "value1" }
# default_tags = {}
#
## Group default sampling interval. If a node in the group doesn't set its
## sampling interval, this is used.
# sampling_interval = "0s"
#
## Node ID Configuration. Array of nodes with the same settings as above.
## Use either the inline notation or the bracketed notation, not both.
#
## Inline notation (default_tags and monitoring_params not supported yet)
# nodes = [
# {name="node1", namespace="", identifier_type="", identifier=""},
# {name="node2", namespace="", identifier_type="", identifier=""}
#]
#
## Bracketed notation
# [[inputs.opcua_listener.group.nodes]]
# name = "node1"
# namespace = ""
# identifier_type = ""
# identifier = ""
# default_tags = { tag1 = "override1", tag2 = "value2" }
#
# [[inputs.opcua_listener.group.nodes]]
# name = "node2"
# namespace = ""
# identifier_type = ""
# identifier = ""
#
# [inputs.opcua_listener.group.nodes.monitoring_params]
# sampling_interval = "0s"
# queue_size = 10
# discard_oldest = true
#
# [inputs.opcua_listener.group.nodes.monitoring_params.data_change_filter]
# trigger = "Status"
# deadband_type = "Absolute"
# deadband_value = 0.0
#
## Multiple event groups are allowed.
# [[inputs.opcua_listener.events]]
# ## Polling interval for data collection
# # sampling_interval = "10s"
# ## Size of the notification queue
# # queue_size = 10
# ## Node parameter defaults for node definitions below
# # namespace = ""
# # identifier_type = ""
# ## Specifies OPCUA Event sources to filter on
# # source_names = ["SourceName1", "SourceName2"]
# ## Fields to capture from event notifications
# fields = ["Severity", "Message", "Time"]
#
# ## Type or level of events to capture from the monitored nodes.
# [inputs.opcua_listener.events.event_type_node]
# namespace = ""
# identifier_type = ""
# identifier = ""
#
# ## Nodes to monitor for event notifications associated with the defined
# ## event type
# [[inputs.opcua_listener.events.node_ids]]
# namespace = ""
# identifier_type = ""
# identifier = ""
## Enable workarounds required by some devices to work correctly
# [inputs.opcua_listener.workarounds]
# ## Set additional valid status codes, StatusOK (0x0) is always considered valid
# # additional_valid_status_codes = ["0xC0"]
# ## Use unregistered reads instead of registered reads
# # use_unregistered_reads = false
Node Configuration
An OPC UA node ID may resemble: “ns=3;s=Temperature”. In this example:
- ns=3 is indicating the
namespace
is 3 - s=Temperature is indicting that the
identifier_type
is a string andidentifier
value is ‘Temperature’ - This example temperature node has a value of 79.0 To gather data from this node enter the following line into the ’nodes’ property above:
{name="temp", namespace="3", identifier_type="s", identifier="Temperature"},
This node configuration produces a metric like this:
opcua,id=ns\=3;s\=Temperature temp=79.0,Quality="OK (0x0)" 1597820490000000000
With ‘DataType’ entered in Additional Metrics, this node configuration produces a metric like this:
opcua,id=ns\=3;s\=Temperature temp=79.0,Quality="OK (0x0)",DataType="Float" 1597820490000000000
If the value is an array, each element is unpacked into a field using indexed keys. For example:
opcua,id=ns\=3;s\=Temperature temp[0]=79.0,temp[1]=38.9,Quality="OK (0x0)",DataType="Float" 1597820490000000000
Group Configuration
Groups can set default values for the namespace, identifier type, tags settings and sampling interval. The default values apply to all the nodes in the group. If a default is set, a node may omit the setting altogether. This simplifies node configuration, especially when many nodes share the same namespace or identifier type.
The output metric will include tags set in the group and the node. If a tag with the same name is set in both places, the tag value from the node is used.
This example group configuration has three groups with two nodes each:
# Group 1
[[inputs.opcua_listener.group]]
name = "group1_metric_name"
namespace = "3"
identifier_type = "i"
default_tags = { group1_tag = "val1" }
[[inputs.opcua.group.nodes]]
name = "name"
identifier = "1001"
default_tags = { node1_tag = "val2" }
[[inputs.opcua.group.nodes]]
name = "name"
identifier = "1002"
default_tags = {node1_tag = "val3"}
# Group 2
[[inputs.opcua_listener.group]]
name = "group2_metric_name"
namespace = "3"
identifier_type = "i"
default_tags = { group2_tag = "val3" }
[[inputs.opcua.group.nodes]]
name = "saw"
identifier = "1003"
default_tags = { node2_tag = "val4" }
[[inputs.opcua.group.nodes]]
name = "sin"
identifier = "1004"
# Group 3
[[inputs.opcua_listener.group]]
name = "group3_metric_name"
namespace = "3"
identifier_type = "i"
default_tags = { group3_tag = "val5" }
nodes = [
{name="name", identifier="1001"},
{name="name", identifier="1002"},
]
Event Configuration
Defining events allows subscribing to events with the specific node IDs and
filtering criteria based on the event type and source. The plugin subscribes to
the specified event_type
Node-IDs and collects events that meet the defined
criteria. The node_ids
parameter specifies the nodes to monitor for events
(monitored items). However, the actual subscription is based on the
event_type_node
determining the events to capture.
Event Group Configuration
You can define multiple groups for the event streaming to subscribe to different
event types. Each group allows to specify defaults for namespace
and
identifier_type
being overwritten by settings in node_ids
. The group
defaults for node information will not affected the event_type_node
setting
and all paramters must be set in this section.
This example group configuration shows how to use group settings:
# Group 1
[[inputs.opcua_listener.events]]
sampling_interval = "10s"
queue_size = "100"
source_names = ["SourceName1", "SourceName2"]
fields = ["Severity", "Message", "Time"]
[inputs.opcua_listener.events.event_type_node]
namespace = "1"
identifier_type = "i"
identifier = "1234"
[[inputs.opcua_listener.events.node_ids]]
namespace = "2"
identifier_type = "i"
identifier = "2345"
# Group 2
[[inputs.opcua_listener.events]]
sampling_interval = "10s"
queue_size = "100"
namespace = "3"
identifier_type = "s"
source_names = ["SourceName1", "SourceName2"]
fields = ["Severity", "Message", "Time"]
[inputs.opcua_listener.events.event_type_node]
namespace = "1"
identifier_type = "i"
identifier = "5678"
node_ids = [
{identifier="Sensor1"}, // default values will be used for namespace and identifier_type
{namespace="2", identifier="TemperatureSensor"}, // default values will be used for identifier_type
{namespace="5", identifier_type="i", identifier="2002"} // no default values will be used
]
Metrics
The metrics collected by this input plugin will depend on the configured
nodes
, events
and the corresponding groups.
Example Output
group1_metric_name,group1_tag=val1,id=ns\=3;i\=1001,node1_tag=val2 name=0,Quality="OK (0x0)" 1606893246000000000
group1_metric_name,group1_tag=val1,id=ns\=3;i\=1002,node1_tag=val3 name=-1.389117,Quality="OK (0x0)" 1606893246000000000
group2_metric_name,group2_tag=val3,id=ns\=3;i\=1003,node2_tag=val4 Quality="OK (0x0)",saw=-1.6 1606893246000000000
group2_metric_name,group2_tag=val3,id=ns\=3;i\=1004 sin=1.902113,Quality="OK (0x0)" 1606893246000000000
Was this page helpful?
Thank you for your feedback!
Support and feedback